Force10 Networks Force10 User Manual Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 105
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
Installing and Maintaining the E1200i System 35
The E1200i AC system requires a minimum of two AC power supplies to operate, three for power
redundancy, four for facility redundancy (2+2), and 6 for 3+3 redundancy. To comply with safety agency
and EMI regulations, you must install the AC-cord retainer over all power cords. The E1200i AC chassis
contains six AC power supply slots, as shown in Figure 11.
Figure 11 E1200i AC Power Supply Shelf
Chapter 7 Installing AC Power Supplies
Note: If you are installing only two power supplies, they must be installed in the same row. FTOS
will generate an error message if the two power supplies are not in the same row.
Note: If you are installing power supplies for redundancy:
For 2+2 redundancy, two power supplies must reside in each row. That is, two in the top row and two in the
bottom row.
For redundant operation with only three power supplies, install all three power supplies in the same row.
Note: The On/Standby switch disconnects power to the rest of the chassis from all 6 AC power
supplies.
When the AC cord is attached, power supply fans will spin and the LEDs will indicate status while the On/
Standby switch is in Standby.
On/Standby
Switch
AC-Cord Retainer
Safety Cover
Power Supplies
AC Power Plugs
This retainer must be in place during normal operation.
Do not remove except for servicing
/
/
/
\
WAR N ING -
HIGH LEAKAGE CURRENT. EARTH CONNECTION
ESSENTIAL BEFORE CONNECTING SUPPLY.
COURANT DE FUITE ELEVE. RACCORDEMENT
A LA TERRE INDISPENSABLE AVANT LE
RACCORDEMENT AU RESEAU.
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 104 105

Comments to this Manuals

No comments